Five areas of expertise, one goal: a fire protection system that works as a whole and meets both your corporate standards and local requirements.
Fire safety systems integration (SSI coordination)
In France, SSI coordination is a defined role under standard NF S 61-931 for public buildings. In industrial sites, it is driven by your insurer’s requirements under the APSAD R7 rule. We analyse your needs, define the functional design and zoning, review contractor submittals, supervise installation and run functional acceptance tests. For US teams, this is close to integrated systems testing under NFPA 4.
Fire detection
Risk analysis, detector selection (spot, beam, linear heat, aspirating, flame), zoning, specifications and acceptance. We target the quality level required by your insurer: N7 certificate, DC7 or DI7 declaration under APSAD R7.
Pre-action, deluge and foam control
We focus on the control side: detector choice, alarm confirmation by double detection, single or double interlock logic, the electrical control and delay unit that releases the valves, and full-chain acceptance testing. Hydraulic design remains with the sprinkler contractor.
Gas fire suppression
Agent selection (inert gases, clean agents or CO₂), detection and release control, delays and abort functions, life safety, bid review, site supervision and acceptance, in line with APSAD R13 and EN 15004. We also help you anticipate EU restrictions on fluorinated agents.
Process interlocks
Scenario analysis, interlock matrix linking each detection event to shutdown actions, interface between the fire safety system and your PLCs, and on-site functional tests.